Summarize egress and ADA issues from the latest QC run for Summit Surgery Center and which sheets they're on.

Based on the latest QC run for Summit Surgery Center, here are the egress and ADA-related issues by sheet.

Issues by sheet

SheetIssueSeverityNotes
A-102Egress path not continuous to exitCriticalRoom 102 egress does not lead to exit without passing through another tenant space
A-104Door width does not meet ADA minimum (30" vs 32" required)CriticalClear width at door on plan is 30"
A-104Toilet room clear floor space under 30" x 48" at lavatoryMajorADA 606.2
A-104Grab bar length insufficient at water closetMajorVerify side grab bar meets 42" minimum
A-103Unlabeled exit sign at egress door to stairMajorAdd exit sign per IBC 1013.1

Summary

SeverityCount
Critical2
Major3
Total5

Recommendations:

  • Resolve both critical items before issuance (egress path and ADA door width).
  • Add exit sign callout on A-103 and verify grab bar/clear floor space dimensions on A-104.
  • Consider a focused ADA review pass on all toilet rooms.
Compare sheet A-102 with the door schedule on A-106 and list any missing or inconsistent doors.

I've compared A-102 (Floor Plan) with A-106 (Door Schedule). Findings below.

Door schedule comparison

Door IDOn plan (A-102)On schedule (A-106)TypeStatus
D101–D1073068 / 90 minMatch
D104Pair shownSingle (D104) listed2868Missing second leaf on schedule
D108No rated callout1-hr fire-rated20 minAdd rated frame note on plan
D109–D1123068Match

Issues

  1. Room 104 – Plan shows a pair of doors; schedule lists only one (D104). Add the second leaf to the schedule or note one as fixed.
  2. D108 (corridor exit) – Schedule shows 1-hour fire-rated assembly; plan has no rated frame callout. Add a note or symbol for the rated assembly on A-102.

Summary

  • Matches: 10 of 12 door references align.
  • Action items: 1 coordination gap (D104 pair), 1 plan note needed (D108 rating).
Demo: input disabled. In the full app you can type and add sheet chips (max 5).