QC Run - 2/5/2026 / QC Report
Generated on February 5, 2026
TOTAL ISSUES
12
CRITICAL
1
Must fix before issuance
MAJOR
6
OVERALL SCORE
82%
Detailed Issues
Door width does not meet ADA minimum
A-104Page 14CRITICALDoor on A-104 is 30" clear width; ADA requires 32" minimum.
Recommended Fix:
Widen door frame to 32" clear opening per IBC/ADA.
Door schedule inconsistency
A-601Page 18MAJORDoor 112B is in door schedule on sheet A-601 but not shown on floor plan sheet A-102.
Recommended Fix:
Add door 112B to floor plan A-102 or remove from schedule; align schedule and plans.
Wall type baseline conflict (A-102 vs A-103)
A-102Page 18MAJORFloor Plan (A-102) general notes state "All walls are S04E unless noted otherwise"; Dimension Floor Plan (A-103) states "All walls are S03E unless noted otherwise." Conflict can cause incorrect wall construction.
Recommended Fix:
Confirm intended typical interior wall type and revise A-102/A-103 notes so typical wall type is consistent across plans and details.
Code edition mismatch
A-103Page 19MAJORDimension Floor Plan legend references "1 HOUR RATED FIRE BARRIER PER 2018 IBC SECTIONS 509 AND 707" and "COMPLYING WITH 2018 IBC SECTION 709." Adopted code for the project is 2021 IBC.
Recommended Fix:
Update all sheet legends to adopted 2021 IBC and confirm section numbering/requirements remain correct.
Template/jurisdiction carryover in roof plan note
A-301Page 21MAJORRoof plan note states "TOWN OF GILBERT" must approve field modifications for rooftop units visibility. Project location is Riverside, California; appears to be boilerplate from another jurisdiction.
Recommended Fix:
Replace with correct AHJ (Riverside, CA) requirements or remove if not applicable. Re-issue roof notes with project-specific AHJ references only.
Door schedule internal conflict: 1-hour vs 2-hour rating
A-601Page 34MAJORDoor 113B shows "1-HOUR RATED" in the assembly rating column but the comments column reads "2Hr Rated Door." Direct internal conflict; high-risk with suite separation rating conflict noted in project.
Recommended Fix:
Confirm required fire rating per governing separation requirement; revise door schedule so rating and comments match. Verify fire-rated hardware/closer.
Door schedule references missing hardware schedule sheets
A-601Page 34MAJORA-601 includes note "REFER TO SHEETS A-605, A-606, A-607 FOR HARDWARE SCHEDULE" but A-606 and A-607 are not in the project sheet index. Prevents full review and coordination of hardware.
Recommended Fix:
Include sheets A-606 and A-607 in the set or correct the note to reference actual hardware schedule sheet locations in the set.
Wall type baseline inconsistent (floor plan vs dimension plan)
A-103Page 18MINORWall type baseline is inconsistent between floor plan and dimension plan (S04E vs S03E).
Recommended Fix:
Align typical wall type in both plan notes.
Corridor wall assembly does not comply with IBC
A-201Page 18MINORCorridor wall assembly at grid B not labeled per IBC; may not meet required rating for occupancy.
Recommended Fix:
Verify assembly and label fire rating per IBC Table 1020.1; revise if needed.
Roof plan keynotes list contains placeholder/blank items
A-301Page 21MINORRoof plan keynotes list contains placeholder or blank items; keynote set is incomplete.
Recommended Fix:
Complete keynote set and remove placeholders before issuance.
Scale inconsistency on detail
S-401Page 22MINORDetail 3/S4.1 scale does not match key plan.
Recommended Fix:
Correct scale or add note to clarify.
Cross-sheet reference to missing hardware sheets (A-606/A-607)
A-601Page 34MINORA-601 references hardware schedule sheets A-606 and A-607 which are not provided in this set.
Recommended Fix:
Include A-606/A-607 in the set or correct the note to actual sheet locations included.