QC Run - 2/1/2026 / QC Report
Generated on February 1, 2026
TOTAL ISSUES
8
CRITICAL
0
Must fix before issuance
MAJOR
4
OVERALL SCORE
88%
Detailed Issues
Door schedule inconsistency
A-601Page 18MAJORDoor 301A is in door schedule on sheet A-601 but not shown on floor plan sheet A-101.
Recommended Fix:
Add door 301A to floor plan or remove from schedule; align schedule and plans.
Wall type baseline conflict (A-101 vs A-102)
A-101Page 18MAJORFloor plan (A-101) notes "All walls S05E unless noted"; dimension plan (A-102) notes "All walls S04E unless noted." Inconsistent baseline can cause wrong construction.
Recommended Fix:
Confirm typical interior wall type and make A-101/A-102 notes consistent.
Code edition mismatch
A-103Page 19MAJORSheet legends reference 2018 IBC; adopted code for the project is 2021 IBC.
Recommended Fix:
Update all legends to 2021 IBC and confirm section numbering.
Door schedule references missing hardware sheets
A-601Page 34MAJORA-601 note references A-606, A-607 for hardware schedule but those sheets are not in the set.
Recommended Fix:
Include A-606/A-607 or correct the note to actual sheet locations in the set.
Wall type inconsistent between floor and dimension plan
A-102Page 18MINORTypical wall type differs between floor plan and dimension plan notes (S05E vs S04E).
Recommended Fix:
Align typical wall type in both plan notes.
Hatch pattern density inconsistent with key
A-302Page 20MINORWall type hatch on A-302 does not match legend density.
Recommended Fix:
Adjust hatch scale to match legend.
Template/jurisdiction carryover in roof plan
A-301Page 21MINORRoof plan note references "City of Phoenix" for RTU screening. Project is Downtown (different jurisdiction)—likely boilerplate.
Recommended Fix:
Replace with correct AHJ or remove; use project-specific AHJ references only.
Roof plan keynotes list contains placeholder/blank items
A-301Page 21MINORRoof plan keynotes list contains blank or placeholder entries; keynote set incomplete.
Recommended Fix:
Complete keynote set and remove placeholders.